Product Gallery
3 images — select thumbnail or expand
IP65 industrial gas transmitter with 4–20 mA output and replaceable plug-in sensor. Detects toxic gases, oxygen and flammable gases. Design by Giugiaro.
Interested in this product?
Contact our team to discuss specifications, pricing, and availability for your site.
Details
Technical specifications and application details.
IP65 industrial gas transmitter with 4–20 mA output and replaceable plug-in sensor. Detects toxic gases, oxygen and flammable gases. Design by Giugiaro.
The TS282 is a gas transmitter that detects toxic gases, oxygen and flammable gases and delivers a proportional 4–20 mA output to a control unit. It shares the IP65 ABS V0 enclosure designed by Giugiaro Design and the plug-in replaceable sensor cartridge with quick-release connector used across the SE/TS platform, enabling easy, non-intrusive sensor replacement.
While the SE237 is a stand-alone detector with relays, the TS282 is the transmitter-only version intended to be wired to a Tecnocontrol control unit (such as the CE408/CE424/CE516/CE700 series). It is powered at 12-24 VDC (−10/+15%, 3 W) and is available with electrochemical, catalytic, pellistor, infrared and semiconductor sensors covering a very broad list of gases and refrigerants.
| Code | Type | Gas / Range |
|---|---|---|
| TS282EA / EA-H | Electrochemical | NH3 |
| TS282EC-S / EC-H | Electrochemical | CO |
| TS282EH | Electrochemical | H2S |
| TS282EO | Electrochemical | O2 |
| TS282ES | Electrochemical | SO2 |
| TS282EN / EN2 | Electrochemical | NO / NO2 |
| TS282ECL / EHCL / EHCN | Electrochemical | Cl2 / HCl / HCN |
| TS282IC2 / IC2-H | Infrared | CO2 (5% Vol / 5000 ppm) |
| TS282KM / KG / KB / KI | Catalytic | CH4 / LPG / Fuel / H2 |
| TS282PM / PG / PB / PI | Pellistor | CH4 / LPG / Fuel / H2 |
| TS282SF1SF5 (-H) | Semiconductor | Refrigerants R134a / R404a / R407c / R410a / R507 |
Industrial plants and car parks where remote 4–20 mA transmitters feed a central control unit for toxic, flammable or oxygen monitoring.
Specifications
Detailed parameters and configurations for this model.
| Parameter | Value |
|---|---|
| Type | Gas transmitter (4–20 mA) |
| Protection rating | IP65 |
| Output | 4–20 mA |
| Power supply | 12-24 VDC (−10/+15%) – 3 W |
| Sensor technologies | Electrochemical / Catalytic / Pellistor / Infrared / Semiconductor |
| Sensor cartridge | Plug-in, replaceable, quick-release |
| Sensor life (clean air) | Catalytic 5 y / Electrochemical 2 y / Pellistor 5 y / Infrared 5 y / Semiconductor 5 y |
| Design | ABS V0 by Giugiaro Design |
Related
Other products in the same category.
Book a consultation with our gas monitoring experts. We provide tailored solutions for any industry across Australia.